Dynamic Radiator System
2-pipe DP above 70 kPa with DPCV
Function
The room temperature is controlled by the radiator valve on each radiator. The balance of the system is handled by the flow setting of the dynamic radiator valves.
A DPCV controlling the differential pressure at every riser limits the DP between 15-70 kPa which is the DP range for the dynamic radiator valves.
The flow at the individual risers is automatically limited and balanced by the dynamic radiator valves regardless of outside pressure fluctuations.
Benefits
- Direct flow setting on each radiator.
- Ensures full balance and flow limitation in the system.
- Provides optimal modulation for the radiator valves.
- All sections will have a defined DP available.
- With the correct dynamic radiator valve flow-setting, the flow will be controlled in every part of the system.
Considerations
- The DP available at the dynamic radiator valves must be within 15-70 kPa.